· Sodeca 400º/2h extraction units, with linear input and output, to work outside the fire risk zone.
· Structure in galvanized steel sheet and turbine with blades.
· Approval according to EN 12101-3, with certification No. 0370-CPR-0594. Direction of the air in a linear sense.
· Class F motors, with ball bearings, IP55 protection, 1 or 2 speeds. IE3 efficiency for powers equal to or greater than 0.75kW, except single phase,
2 speeds and 8 poles. Three phase 230 / 400V-50Hz. (Up to 4kW) and 400 / 690V-50Hz (powers greater than 4kW).
· Maximum temperature of the air to be transported: Service S1 -20ºC + 120ºC in continuous. Service S2 300ºC / 2h and 400ºC / 2h.
· Anticorrosive finish in galvanized steel.